Post Jobs

GESTRA BK45 PDF

(Bimetallic) Regulator PN 40 – PN BK 45, BK DN 15, 20, • Robust regulator for roughest operating conditions (unaffected by waterhammer and frost ). Features and Benefits. • Forged steel body and cover. • Pressure assisted fail- open design. • Factory-preset bimetallic regulator with integral staged nozzle. BK BK 45U. BK Installation Instructions Steam Traps BK 45, BK 45U, BK GESTRA Steam Systems. EN. English.

Author: Vudoramar Akigul
Country: Burkina Faso
Language: English (Spanish)
Genre: Marketing
Published (Last): 23 June 2008
Pages: 495
PDF File Size: 18.5 Mb
ePub File Size: 3.55 Mb
ISBN: 349-8-18283-445-2
Downloads: 37981
Price: Free* [*Free Regsitration Required]
Uploader: Samuzahn

Flowserve Bk 45 Steam Trap 3/4″ NPT 22 Bar BK45 | eBay

In steam traps with GESTRA Thermovit regulators, the opening and closing process is controlled by the interaction of bimetallic plates and a stage nozzle. However, the temperature-induced deflection of the duo stainless steel plates is not sufficient to generate the required force to counter the valve force acting on the nozzle needle in the opening direction gdstra the entire operating range.

Acting against this thermal process is the operating pressure and pressure that builds up in the chamber of the stage nozzle due to flash steam thermodynamic process. Saturated steam pipes Superheated steam pipes Trace heaters Air heaters Thanks to automatic venting, steam traps from the BK series are also ideal for use as air vents.

  KATHARINE KOLCABA COMFORT THEORY PDF

Bimetallic Steam Trap BK45

This way, thermal and spring properties are coordinated in such a way that the opening and closing temperatures are always just a few degrees below boiling point. Especially recommended for use in: Thermostatic steam traps for removing condensate from steam or for venting steam pipes.

It is precisely this principle that makes steam traps from the BK series highly responsive, very efficient and extremely resistant. Just below saturation temperature, the bimetallic plates are deflected to such an extent that the orifice is almost closed.

As the temperature of the condensate rises, the duo stainless steel plates deflect and pull the stage nozzle in the closing direction. Use Robust steam traps for condensate removal from heating bk455 with small load fluctuations. Robust steam traps for condensate removal from heating processes with small load fluctuations.

When the system starts up and on the formation of cold condensate and air, the duo stainless steel plates lie flat.

BK 45/46 – Gestra

The operating pressure acts in the direction of opening, so that the valve is opened fully. Immediately below saturation temperature boiling pointthe duo stainless steel plates are deflected to such an extent that the orifice is almost completely closed.

Be the first to review! Advantages Extremely good start-up performance No loss of steam Suitable for differential pressure up to bar Able to cope with the harshest operating conditions Any installation position — in horizontal or vertical pipes Inner parts made of corrosion-resistant stainless steel Can be serviced without removing the body from the pipe Metal base bushing provides the seal between the body and bimetallic regulator Stage nozzle for non-return valve action Wear-resistant.

  HX4700 MANUAL PDF

The opening and closing process is controlled by the interaction of the stage nozzle and gk45 temperature sensor, which consists of duo stainless steel plates. As the temperature of the condensate rises, the bimetallic plates deflect and pull the stage nozzle in the closing direction.

Method of Operation The steam trap is fully open when the system starts up.

Therefore, the column of these plates consists of a spring with a characteristic that is adapted to the valve force, which changes under pressure. This state of equilibrium between the temperature-induced closing and pressure-induced opening forces determines the outlet cross section.

Thermostatic steam traps BK 45/46

The pressure in the stage nozzle chamber therefore drops and, as the amount of flash steam declines, dissipates altogether. Cold condensate and air are discharged.

Especially recommended for use in:.